POWERFLOR USA, INC.
SYSTEM SPECIFICATIONS
Section 16128-Undercarpet Cabling System
Part I - GENERAL
1.01 WORK SUMMARY
- A. Contractor shall provide submittals, materials, and
installation of the floor system as shown on the contract drawings and as specified in this document.
1.02 RELATED WORK NOT INCLUDED
- A. General contractor shall provide clear access, dry secure
storage, and a clean subfloor area, which is free of construction debris and other trades during installation of the floor system. Area to receive the floor system shall be enclosed and maintained at a temperature range of 40 to 90 F and a humidity range of 20%
to 70% relative.
B. Electrical contractor shall provide necessary material and labor to electrically connect the floor system electrical components to the building.
C. Communications contractor shall provide necessary
material and labor to connect the tele/data to the building wiring closet.
1.03 SYSTEM DESCRIPTION
- A. Low Profile Wire Management floor system shall consist of
2-5/8 inch high by 9 inch square polycarbonate pedestals united with four identical units. Providing an 18 inch by 18 inch unit to which a carpet tile is adhered. The 18 inch square panel assemblies are laid onto a level floor over 1/8 inch thick Volara polyurethane foam. Panels are placed loose to achieve accessibility.
B. Individual panels shall accommodate power and
voice/data outlets as manufactured by POWERFLOR.
C. Perimeter panels available in 18 inch by 9 inch
configurations for edge trimming.
D. Carpet tile color and pattern selection shall be
selected by architect and/or owner. Carpet tile shall be compatible with POWERFLOR production standards.
E. Finished Floor height of the system above the subfloor shall be a nominal 3 inches.
F. Ramps: Access ramps are compliant with the Americans
with Disabilities Act (ADA).
G. Electrical Components: AMPINNERGY Power System, by TYCO ELECTRONICS, INC.. UL183 listing. Manufactured Wiring System, National Electric Code, Sections 604 and 605.
H. Complete cable system, both energy and tele/data must
be quick connect/disconnect.
1.04 SHOP DRAWINGS AND PRODUCT DATA
- A. Submit drawings showing complete floor system including
floor panel layout and all accessories that are a part of the system.
- B. Submit details and descriptive notes for product data,
warranty and maintenance.
1.05 SAMPLES
- Submit for approval one full size floor panel with finished
surface and understructure components.
1.06 QUALITY ASSURANCE
- Submit certified laboratory test data for approval, which
indicates that the supplied system complies with the performance, indicated herein.
All Technical Data is From POWERFLOR USA INC. in house Data!
Products Specs
| Installation Specs
| Test Data Specs