DOCUMENTATION AND OTHER VENDOR REQUIREMENTS FOR UPS UNINTERRUPTABLE POWER SUPPLIES ELECTRICAL SAFETY REPORT COVERING: AS 62040.1.1:2013 Uninterruptible power systems (UPS) - General and safety requirements for UPS used in operator access areas AS/NZS 62368.1:2022 Audio/video, information and communication technology equipment - Part 1: Safety requirements (replaces earlier AS/NZS60065 and 60950 standards). EMC REPORT COVERING: AS/NZS CISPR 32:2015 Electromagnetic compatibility of multimedia equipment - Emission requirements This supersedes both AS/NZS CISPR13 and AS/NZS CISPR22 This is required for the main product. If a plugpack power supply is bundled with it, then either the CISPR32 report should include that adaptor, or a separate report be supplied for the adaptor. OTHER MANDATORY REQUIREMENTS: CORD Current Australian Approvals Certificates are required for: • The mains cord • The mains plug • The appliance connector (if a detachable cord is used). Note that this is IN ADDITION to the Approval Certificate for the appliance itself, if applicable. • The components of the cord must be marked in accordance with the requirements of their approval certificates. • The length of cords supplied in production product must match the length of the evaluated sample.