LG Thermal Overload Relay

      ¡P Rated Current (AC400V) From 0.1A to 800A. ¡P Direct Mounting Type TOR so that an additional Bracket is not necessary.   ¡PFinger-proof safety cover of Thermal Overload Relays prevent careless touch of electric conductor. ¡P Separation of Power Part and Operation Part prevents Short Circuit. ¡P 3 Steps Current Setting: Manual, Auto Reset and Trip Indicator. 

Select the Suitable Thermal Overload Relay for Details Information.

Suitable Thermal Overload Relay Type Adjustable
Current Ranges
Rated
Current (A)
Full Load Current in motor (4 Pole)
440V 60Hz 220V 60Hz
P (kW) In(A) P (kW) In(A)
GTH-22 0.1~0.16 0.14 - - - -
0.16~0.25 0.21 - - - -
0.25~0.4 0.33 0.1 0.36 - -
0.4~0.63 0.52 - - - -
0.63~1 0.82 0.2 0.7 0.1 0.71
1~1.6 1.3 - - 0.2 1.4
1.6~2.5 2.1 0.75 1.8 0.4 2.4
2.5~4 3.3 1.5 3.3 0.75 3.6
GTH-22 , GTH-40 4~6 5 2.2 4.6 - -
5~8 6.5 - - 1.5 6.5
6~9 7.5 3.7 7.5 - -
GTH-22 , GTH-40 , GTH-85 7~10 8.5 - - 2.2 9.2
9~13 11 5.5 11 - -
12~18 15 7.5 15 3.7 15
16~22 19 - - - -
GTH-40 , GTH-85 18~26 22 11 21 5.5 22
24~36 30 15 28 7.5 30
28~40 34 18.5 34 - -
GTH-85 , GTH-100 , GTH-150 34~50 41 22 39 11 42
GTH-100 , GTH-150 39~57 48 - - - -
GTH-85 45~65 55 30 54 15 55
GTH-100 , GTH-150 43~65 56
GTH-85 54~75 65 37 66 18.5 67
GTH-100 , GTH-150 54~80 67
GTH-85 63~85 74 - - - -
GTH-100 , GTH-150 , GTH-220 65~100 80 45 80 22 78
GTH-100 , GTH-150 , GTH-220 , GTH-400 85~125 107 55 99 30 107
GTH-150 100~150 130 75 135 37 132
GTH-220 , GTH-400 100~160
120~180 150 90 160 45 160
160~240 200 110 192 55 198
GTH-400 , GTH-600 200~300 250 132 226 - -
260~400 350 200 330 90 320
GTH-600 400~600 500 - - 132 452
520~800 660 - - 160 530

¡@

Hosted by www.Geocities.ws

1