Aplikasi tekno-ekonomi
Link tekno-ekonomi Panel Tegangan Rendah 400 Volt
GE PT Guna Elektro http://www.gae.co.id/gae/index.asp
MG Merlin Gerin www.schneider-electric.co.id
MG - Telesindo http://telesindo-electric.com
Siemens www.siemens.co.id
UME - Uni Makmur Elektrika [email protected]
Kontrol Ragam - Switch Boards [email protected]
SIER Switch Boards www.sier.co.id/isi1.html
INDUSTIRA Switch Boards www.industira.com/website1.asp
Testing Calibration - LMK http://www.pln-litbang.co.id/beta
Kalkulasi hubung singkat 3-fasa untuk menentukan
Breaking Capacity suatu Circuit Breaker di sisi TM/TR Trafo
General Electric Tools for Electrical Calculation
http://www.geindustrial.com/solutions/consultants/docs/Xfmr.xls
http://www.geindustrial.com/solutions/engineers/usefultools.html
Kalkulasi arus hubung singkat instalasi listrik bangunan yang menggunakan
transformator minyak 20 KV / 400 Volt
Download hitungan yang sudah diformulasi sbb :
http://www.geocities.com/kelistrikan/Kalkulasi_arus_hubung_singkat.ppt
Rated KVA Trafo | Arus Nominal sisi Primer (Amp) | Arus Nominal sisi Sekunder (Amp) | Impedansi Zsc (%) |
Arus hubung singkat sisi Primer (kA) *) |
Rasio Xsc/R *) |
MVA hubung singkat(HS)
|
kA hubung singkat sisi sekunder | kA 50% kontribusi HS dari beban motor | kA hubung singkat total | kA Breaking Capacity dari Circuit Breaker |
25 | 0.7 | 36 | 4% | 20 | 10 | 693 | 0.9 | 0.07 | 0.97 | 10 |
50 | 1.4 | 72 | 4% | 20 | 10 | 693 | 1.8 | 0.14 | 1.95 | 10 |
100 | 2.9 | 144 | 4% | 20 | 10 | 693 | 3.6 | 0.29 | 3.88 | 10 |
160 | 4.6 | 231 | 4% | 20 | 10 | 693 | 5.74 | 0.46 | 6.2 | 15 |
200 | 5.8 | 289 | 4% | 20 | 10 | 693 | 7.17 | 0.58 | 7.74 | 15 |
250 | 7.2 | 361 | 4% | 20 | 10 | 693 | 8.94 | 0.72 | 9.66 | 20 |
315 | 9.1 | 455 | 4% | 20 | 10 | 693 | 11.24 | 0.91 | 12.15 | 25 |
400 | 11.5 | 577 | 4% | 20 | 10 | 693 | 14.23 | 1.15 | 15.38 | 25 |
500 | 14.4 | 722 | 4% | 20 | 10 | 693 | 17.72 | 1.44 | 19.17 | 35 |
630 | 18.2 | 909 | 4% | 20 | 10 | 693 | 22.23 | 1.82 | 24.05 | 35 |
800 | 23.1 | 1155 | 4.5% | 20 | 10 | 693 | 25.02 | 2.31 | 27.33 | 35 |
1000 | 28.9 | 1443 | 5% | 20 | 10 | 693 | 28.06 | 2.89 | 30.95 | 50 |
1250 | 36.1 | 1804 | 5.5% | 20 | 10 | 693 | 31.76 | 3.61 | 35.37 | 50 |
1600 | 46.2 | 2309 | 6% | 20 | 10 | 693 | 37.06 | 4.62 | 41.68 | 65 |
2000 | 57.7 | 2887 | 6% | 20 | 10 | 693 | 45.91 | 5.77 | 51.68 | 65 |
2500 | 72.2 | 3609 | 7% | 20 | 10 | 693 | 49.02 | 7.22 | 56.24 | 75 |
*) Jika data hubung singkat sumber PLN tidak diketahui maka diasumsikan arus hubung singkat sisi primer 20 KV adalah 20 kA dengan rasio Reaktansi hubung singkat (subtransient) terhadap resistansi Xsc/ R = 10 ( range antara 5 ~ 12)