Heating
Home Up Trips States US Canada

 

RV Furnace Trouble Shooting

Warning:We recommend that only qualified technicians work on furnaces.
Do It Yourself at your own risk.
You are responsible for all safety precautions and leak checking.

Before attempting to trouble shoot your furnace be sure you understand the sequence of operation. Also see definitions.

This list is a guide only, of the more common causes of furnace failure, it is by no means complete.

Electronic Ignition Models (DSI)

Before going through the list below, these items should be checked.
Gas Pressure should be 11" of water column.
Power supply, DSI furnaces require 10.5 VDC to 13.5 VDC to operate.
Ducting, check for the correct number of unrestricted ducts and outlets.
Check the return air path, be sure it meets the required minimum sq. in.
RV furnaces are not approved for use with filters.

Blower doesn't run
Possible causes:
no power
thermostat
Warning: Never cross the thermostat wires with the thermostat connected. You will destroy the thermostat.
dirty contacts
bad on/off switch
broken or shorted wires
bad thermostat
bad time delay relay or thermostat relay
You have time delay relay if there is normally a delay from the time you turn the thermostat up to the time the fan actually comes on, usually around 30 seconds.
Instant on blower = thermostat relay
loose or broken wire or poor ground
tripped circuit breaker or blown fuse - not all furnaces have either of these
bad motor
Blower runs - no ignition
Possible Causes:
low voltage
bad fan motor
bad gas supply or low pressure
exhaust or intake vents obstructed
bad or dirty sail switch
bad limit switch
bad or out of adjustment electode
bad electrode wire
bad gas valve
dirty burner
bad control board
NOTE: the design of electronic ignition furnaces is such that once the thermostat closes and calls for heat the blower will run until the thermostat is satisfied, the battery runs to low to run the motor, the motor wears itself out or the thermostat is shutoff.
Burner ignites - goes out after a few seconds
Possible causes:
low gas pressure
intake or exhaust vents obstructed
dirty burner
electrode(s) out of adjustment, dirty, or defective
bad control board
Sooting - usually shows as a black streak above the exhaust vent.
Possible causes:
dirty burner - common with older models that use a cast iron burner
low gas pressure
intake or exhaust vent obstructed
bad fan motor
insufficient heat
Possible causes:
low gas pressure
poor gas supply - crimped gas line, under size tanks in below freezing temps.

This is generic and applies to most DSI model furnaces.
Thermostat calls for heat.
Thermostat relay or time delay relay is energized and allows power to the blower.
Blower motor runs up to speed.
Sail switch closes at 75% of rated blower speed.
Power goes through the limit switch to the ignition control board.
The control board begins trial for ignition, opening gas valve and initiating ignition spark.
Burner ignites.
Thermostat reaches setting and opens.
Burner shuts down.
Fan runs briefly to cool furnace.

Definitions:

sail switch - micro switch with an arm that extends into the blower air stream which closes when the blower reaches approximately 75% of its rated speed. Also called an air prover switch.

limit switch - safety switch, a normally closed switch that opens if it gets to hot, opening turns off power to the gas valve and igniter board

fan switch - a normally open switch that closes at a preset temperature, causes the furnace to run for a short time after the thermostat opens, allowing the furnace to cool down.

time delay relay - same function as fan switch, only has its own heater

igniter electrode - similar to a spark plug, 2 versions, 3 probe (remote sense) or 2 probe (local sense)

ignition control board - when powered, initiates gas valve opening and spark sequence which lasts approximately 7 seconds. Older models are 1 try, thermostat must be cycled off for at least 10 seconds before another ignition cycle is attempted. Newer boards are 3 try, will attempt to ignite 3 times at approximately 60 second intervals.

gas pressure - LP gas pressure must be 11" of water column (6.25 oz per sq. in.), checking and adjusting requires a manometer.

 

Hosted by www.Geocities.ws

1