Residential Electrical Codes

 

Loads:

1.                  14/2 Maximum of 10 devices

2.                  12/2 Maximum of 12 devices

 

Dedicated 12/2 GFI Line:  (20 Amp)

1.      Washing Machine

2.      Refrigerator

3.      Garbage Disposal

4.      Sump Pump

5.      Sewage Ejection

 

Dedicated Line:

1.                  Dishwasher (15 Amp)

2.                  Trash compactor (20 Amp)

3.                  Microwave (20 Amp)

4.                  Furnace

 

GFI Lines:  (Maximum of 3 outlets in series on load side)

1.     Bathroom Outlets  (Allowed to group bathroom outlets together from various locations)

a.      20 amp required with 12/2 cable

b.      One receptacle is required to be adjacent to each basin in every bathroom

2.     Kitchen Counter (Outlet every 2’ & required for wall counter 12” or wider)

a.      20 amp required with 12/2 cable

b.      Only 4 or 6 outlets per circuit depends on county

c.       Islands 12” or wider must have at least one receptacle

3.     At least 1 outlet in garage all must be on GFI

4.     At least 1 outlet required in front of the house

5.     At least 1 outlet required in back of the house

6.     Outlet required in attic & crawl space

7.     Wet bars

8.     Sheds

 

Outlet Requirements:

1.                  Outlet required on walls 2’ or more

2.                  Outlets required every 6’ or 8’ depending on county

3.                  Outlet required in hallway 10’ or more

4.                  At least 1 receptacle in unfinished basement. (GFI required.)

5.                  No outlet may be installed over an electric baseboard heater.

6.                  Receptacles installed in the floor must be a box/ receptacle combination designed specifically for that purpose.  (Receptacles installed in the floor with 18” of the walls may be used in place of the wall mounted outlet.)

 

Light Requirements:

1.     At least one wall switch-controlled outlet or light is required in every habitable room (bathroom, hallways, stairways, attached garage, detached garage with electrical power, and outdoor entrances and exits.)

2.     The lighting outlet for interior stairways must have a wall switch at each floor level where the difference between the floor level is six steps or more.

3.     Bathroom Lights on dedicated circuit (Allowed to group bathroom lights together from various locations)

4.     At least one switch controlled light is required in attic, crawl space, utility room, and any space used for storage or that contain equipment requiring servicing.

 

Smoke Detectors:

1.                  Smoke detectors in bedrooms, hallways, living rooms, dens & basement (even if unfinished) must be on bedroom circuit.

2.                  Must be mounted within 12” of the peak of the highest point of the ceiling.

3.                  Must be mounted 12” from the wall.

 

General Requirements:

9.     Staple within 8” of plasic box and every 4-1/2 feet thereafter.

10.            Staple within 12” of metal boxes, utilizing approved connectors

11.            Staple within 8” of light can

12.            Cable must be 1-1/4” from the nearest edge of the framing member where nails or screws may penetrate the cable, if this distance cannot be maintained the cable must be protected by a steel plate or sleeve at least 1/16” thick.

13.            Individual staple for 12/3 and 14/3 wires

14.            Allowed to group only 2 wires together of 12/2 and 14/2 (doesn’t matter which combination)

15.            Use 3M Stackers where more than 2 wires are or when next to 12/3 or 14/3 wires.

16.            Bedrooms must be on ARC Fault breakers

17.            Three or more wires into a box must be pig-tailed

18.            All service equipment and electrical panels must have a clear area of 30” wide and 36 “ deep in front. (This clear area must extend from floor to ceiling with no intrusions from other equipment, cabinets, counters, appliances.)

19.            Panels are not allowed in clothes closets or bathrooms.

20.            All service equipment must be large enough to supply the connected load.

a.      100 AMPS use 4 AWG Copper or 2 AL-AWG Aluminum & Copper Clad

b.      125 AMPS use 2 AWG Copper or 1/0 AL-AWG Aluminum & Copper Clad

c.       150 AMPS use 1 AWG Copper or 2/0 AL-AWG Aluminum & Copper Clad

d.      175 AMPS use 1/0 AWG Copper or 3/0 AL-AWG Aluminum & Copper Clad

e.      200 AMPS use 2/0 AWG Copper or 4/0 AL-AWG Aluminum & Copper Clad

f.        225 AMPS use 3/0 AWG Copper or 250kcmil AL-AWG Aluminum & Copper Clad

g.      250 AMPS use 4/0 AWG Copper or 300kcmil AL-AWG Aluminum & Copper Clad

h.      300 AMPS use 250kcmil AWG Copper or 350kcmil AL-AWG Aluminum & Copper Clad

i.        350 AMPS use 350kcmil AWG Copper or 500kcmil AL-AWG Aluminum & Copper Clad

j.        400 AMPS use 400kcmil AWG Copper or 600kcmil AL-AWG Aluminum & Copper Clad

21.            The main service equipment panel must be mounted either outside or inside the dwelling as near as possible to the point of entrance of the service conductors to the building.

22.            The main service equipment panel must be grounded to a ground rod and to a water bond, which is the incoming water line.

23.            In main service equipment panels, the neutral and equipment grounding conductors are bonded together.

24.            The neutral in the main service equipment panel, must be bonded to the service enclosure, the bond screw must be green in color, and the grounding electrode system.

25.            In sub-panels the neutral is isolated from the ground.

a.      #6 copper for 100 AMP

b.      #4 copper for 200 AMP

26.            All cables must include a ground conductor

27.            Requirements for Copper NM Cable type (aka romex)

a.      #14 Copper NM Cable type for 15 ameres

b.      #12 Copper NM Cable type for 20 ameres

c.       #10 Copper NM Cable type for 30 ameres

d.      #8 Copper NM Cable type for 50 ameres

e.      #6 Copper NM Cable type for 65 ameres

f.        #4 Copper NM Cable type for 80 ameres

28.            All romex must have a 90 degree conductor insulation rating.

a.      #14 and #12 is used for lighting and receptacle circuits

b.      10/2 is used for electric water heaters.

c.       10/3 with ground for electrical dryers.

d.      8/3 is used for cooktops.

e.      6/3 with ground for ranges and wall mounted ovens.

f.        Ranges and clothes dryers must be wired with four wires.

29.            Requirements for S.E. and S.E.R. Aluminum Cable (Use aluminum antioxidant on all aluminum connections.)

a.      #8 S.E. and S.E.R. Aluminum Cable type for 40 ameres

b.      #6 S.E. and S.E.R. Aluminum Cable type for 50 ameres

c.       #4 S.E. and S.E.R. Aluminum Cable type for 60 ameres

d.      #3 S.E. and S.E.R. Aluminum Cable type for 70 ameres

e.      #2 S.E. and S.E.R. Aluminum Cable type for 90 ameres

 

Electric Heat Circuits

1.                  15 Amperes – Maximum Wattage is 2,880 Watts

2.                  20 Amperes – Maximum Wattage is 3,840 Watts

3.                  30 Amperes – Maximum Wattage is 5,760 Watts

Hosted by www.Geocities.ws

1