Equipos Especiales Refrigeración y Aire Acondicionado Industrial |
|
|
|
|
|
EVAPORADORES ENFRIADORES
DE AGUA SERIE XT&TWC TIPO
TUBO EN TUBO REFRIGERANTE HCFC 22
|
|
|
|
MODELO |
CAP TR |
CONEXIONES |
DIMENSIONES
EN MM |
|||
|
REFRIGERANTE |
AGUA |
L |
W |
H |
||
|
ET&TDX
- 2 |
2 |
1/2
” ODS |
1/2
” |
400 |
400 |
100 |
|
ET&TDX
- 3 |
3 |
5/8 ” ODS |
3/4
” |
450 |
450 |
150 |
|
ET&TDX
- 5 |
5 |
7/8 ” ODS |
|
500 |
500 |
200 |
|
ET&TDX
- 6 |
6 |
7/8 ” ODS |
|
500 |
500 |
250 |
|
CAPACIDAD Y
CAIDA DE PRESION PARA EL CAUDAL DE AGUA CORRESPONDIENTE , HCFC 22 |
|||||||||||||||||||
|
RANGO |
|
|
|
||||||||||||||||
|
APROXIMACION |
|
|
|
|
|
|
|
|
|
||||||||||
|
MODELO |
TR |
MBH |
PSI |
MBH |
PSI |
MBH |
PSI |
MBH |
PSI |
MBH |
PSI |
MBH |
PSI |
MBH |
PSI |
MBH |
PSI |
MBH |
PSI |
|
ET&TDX - 2 |
2 |
19.7 |
1.5 |
23.1 |
2.0 |
26.2 |
2.6 |
20.6 |
1.0 |
24.0 |
1.4 |
26.8 |
1.8 |
22.2 |
0.8 |
24.8 |
1.0 |
28.1 |
1.3 |
|
ET&TDX - 3 |
3 |
29.5 |
1.4 |
34.6 |
1.9 |
39.3 |
2.4 |
30.9 |
1.0 |
36.0 |
1.3 |
40.2 |
1.6 |
33.3 |
0.8 |
37.2 |
1.0 |
42.2 |
1.2 |
|
ET&TDX - 5 |
5 |
49.2 |
1.6 |
57.7 |
2.2 |
65.5 |
2.8 |
51.5 |
1.1 |
60.0 |
1.5 |
67.1 |
1.9 |
55.4 |
0.9 |
61.9 |
1.1 |
70.3 |
1.4 |
|
ET&TDX - 6 |
6 |
59.0 |
1.9 |
69.2 |
2.6 |
78.6 |
3.4 |
61.8 |
1.3 |
72.0 |
1.8 |
80.5 |
2.3 |
66.5 |
1.1 |
74.3 |
1.3 |
84.4 |
1.7 |
CAUDAL = ( Btu / Hr ) / ( 500 x RANGO ) , en GPM de Agua
RANGO = Temperatura Entrada Agua Menos Temperatura Salida Agua , °F
APROXIMACION = Temperatura Salida Agua Menos Temperatura Evaporación Refrigerante , °F
Los datos de Capacidad arriba indicados , están basados en :
Rango
Aproximación
Liquido
refrigerante entrando a 100 ° F , Sobrecalentamiento
en
Factor de ensuciamiento 0.0005
°F = °C x 1.8 + 32
, Btu / Hr
= 0.293 W , Btu / Hr = 0.252 Kcal / Hr , Galon
=
|
|
El Rey
del Frío Ltda Atención : Carlos Barrantes
, Ing. Oficina
: Calle 68B N° 64 - 52 ,
Barranquilla , Colombia Teléfonos
+57 +5 344 1890 , +57 + 316 248 8882 www.geocities.com/elreydelfrio
Edición
08.04.06 |
|
|