TO FIND | DIRECT CURRENT | ALTERNATING CURRENT | |
Single Phase |
Three phase | ||
Amperes When Horsepower (Input) is Known |
HP x 746 Volts x Efficiency |
HP x 746 Volts x Efficiency x PF |
HP x 746 Volts x 1.73 x PF |
Amperes When Kilowatts is Known |
KW x 1000 Volts |
KW x 1000 Volts x PF |
KW x 1000 Volts x 1.73 x PF |
Amperes When kva is Known |
KVa x 1000 Volts |
KVa x 1000 Volts x 1.73 | |
Kilowatts |
Amperes x Volts 1000 |
Amperes x Volts x PF 1000 |
Amperes x Volts x 1.73 x PF 1000 |
kva |
Amperes x Volts 1000 |
Amperes x Volts x 1.73 1000 | |
Power Factor |
Kilowatts x 1000 Amps x Volts or KWA Kva |
Kilowatts x 1000 Amps x Volts x 1.73 or KWA Kva | |
Horsepower (Output) |
Amps x Volts x Efficiency 746 |
Amps x Volts x Efficiency x PF 746 |
Amps x Volts x 1.73 x Efficiency x PF 746 |
These calculators will assist you in determining what size
generator you may require or how to convert one unit of electricity to
another.
Sizing Data - Power Consumption
Generator Size to Start Motors Instructions: You only need to fill in the columns coloured
in blue.
* Please NOTE the above calculations are an estimate only because other factors such as site conditions, motor efficiencies and iron losses are not taken into consideration. |