Power Calculator

TO FIND DIRECT CURRENT ALTERNATING CURRENT
   

Single Phase

Three phase

Amperes When
Horsepower (Input)
is Known

     HP x 746      

Volts x Efficiency

     HP x 746      

Volts x Efficiency x PF

     HP x 746      

Volts x 1.73 x PF

Amperes When
Kilowatts is Known

     KW x 1000      

        Volts

KW x 1000      

  Volts x PF

KW x 1000      

  Volts x 1.73 x PF

Amperes When
kva is Known
 

    KVa x 1000      

        Volts

   KVa x 1000      

        Volts x 1.73

Kilowatts

   Amperes x Volts   

        1000

  Amperes x Volts x PF  

        1000

  Amperes x Volts x 1.73 x PF  

                 1000

kva  

  Amperes x Volts   

        1000

  Amperes x Volts x 1.73  

          1000

Power Factor  

  Kilowatts x 1000   

     Amps x Volts

or 

KWA

Kva

  Kilowatts x 1000   

 Amps x Volts x 1.73

or 

KWA

Kva

Horsepower
(Output)

Amps x Volts x Efficiency

               746

Amps x Volts x Efficiency x PF

                    746

Amps x Volts x 1.73 x Efficiency  x PF

                       746

These calculators will assist you in determining what size generator you may require or how to convert one unit of electricity to another.

They calculate:
Amperes when kVA is known
Converting kVA to kW
Converting kW to kVA
Converting kW to HP
kVA Required to run motors
Guide to units:
HP = Horsepower
kW = Kilo Watts
kVA = Kilo Volt Amps
I = Ampere or Current
V = Volts
PF = Power Factor

Sizing Data - Power Consumption

Calculating Ampere (I), given kVA.
Phase
1, 2, 3
Generator
kVA
Volts
Required
= Ampere
I

Converting kVA to kW
kVA = kW
Converting kW to kVA
kW = kVA

Converting kW to HP
kW = HP

What size genset is needed to start a 3 phase electric motor Direct on Line (DOL) start

HP of
Motor
= Generator
kVA Required

Generator Size to Start Motors

Instructions: You only need to fill in the columns coloured in blue.
Fill in the HP of the motor(s) in their starting squence, select the start method (Direct On Line or Star Delta) and press Evaluate. The required generator size will then be displayed at the bottom.

3 Phase (415 volt @ 50Hz)
1 Phase (240 volt @ 50Hz)

Starting Sequence Motor HP Start Method
DOL / StarDelta
Run Variable Phase Current Starting Value Total Run Current Total Start Current
1 /
2 /
3 /
4 /
5 /
6 /
Generator Size for Starting with: kVA*
Generator Size for Running with: kVA*
Generator Size Recommended: kVA*

 

* Please NOTE the above calculations are an estimate only because other factors such as site conditions, motor efficiencies and iron losses are not taken into consideration.